Description of device functions Proline Prowirl 73
174 Endress+Hauser
ALARM DELAY Description
Use this function to enter a time span for which the criteria for an error always have to be
satisfied before a fault or notice message is generated. Depending on the setting and the
type of error, this suppression acts on the display, the current output and the frequency
output.
!
Note!
If this function is used, fault and notice messages are delayed by the time corresponding
to the setting before being forwarded to the higher-level controller (PCS, etc.). Therefore,
check in advance whether a delay of this nature could affect the safety requirements of
the process. If fault and notice messages may not be suppressed, a value of 0 seconds
must be entered here.
User input
0 to 100 s (in steps of one second)
Factory setting
0 s
SYSTEM RESET Description
Use this function to restart (reset) the measuring device.
Options
NO
The device is not restarted.
RESTART SYSTEM
Restart without disconnecting main power. In doing so, all the data (functions) are
accepted unchanged.
RESET DELIVERY
Restart without disconnecting main power. In the process, all the data (functions) are
reset to the factory setting apart from the sensor data.
Factory setting
NO
TROUBLESHOOTING Description
Use this function to acknowledge system errors for data/checksum errors.
If a data/checksum error occurs (# 029, # 111 ä 64), the associated error block is
displayed in this function and the functions of the error block are reset to the factory
setting.
Only the system error in question is acknowledged if the error block is selected in this
function.
Display
CANCEL
The error block in which a data/checksum error occurred appears on the display.
OPERATION HOURS Description
The hours of operation of the device appear on the display.
Display
Depends on the number of hours of operation elapsed:
Hours of operation < 10 hours display format = 0:00:00 (hr:min:sec)
Hours of operation 10 to 10 000 hours display format = 0000:00 (hr:min)
Hours of operation > 10 000 hours display format = 000000 (hr)
Function description, SUPERVISION group