Electrical connection Proline Prowirl F 200 PROFIBUS PA
30 Endress+Hauser
Connecting cable (reinforced)
Cable, reinforced
2 × 2 × 0.34 mm
2
(22 AWG) PVC cable with common shield (2 pairs, pair-
stranded) and additional steel-wire braided sheath
Flame resistance According to DIN EN 60332-1-2
Oil-resistance According to DIN EN 60811-2-1
Shielding Galvanized copper-braid, opt. density approx. 85%
Strain relief and
reinforcement
Steel-wire braid, galvanized
Cable length 5 m (16 ft), 10 m (32 ft), 20 m (65 ft), 30 m (98 ft)
Operating temperature When mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
can move freely: –25 to +105 °C (–13 to +221 °F)
Cable diameter
Cable glands supplied:
M20 × 1.5 with cable  6 to 12 mm (0.24 to 0.47 in)
Plug-in spring terminals for device version without integrated overvoltage protection:
wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
Screw terminals for device version with integrated overvoltage protection: wire cross-
sections 0.2 to 2.5 mm
2
(24 to 14 AWG)
Fieldbus cable specification
PROFIBUS PA
Cable type
In accordance with IEC 61158-2 (MBP), cable type A is recommended. Cable type A has a
cable shielding that guarantees adequate protection from electromagnetic interference
and thus the most reliable data transfer.
The electrical data of the fieldbus cable have not been specified but determine important
characteristics of the design of the fieldbus, such as distances bridged, number of users,
electromagnetic compatibility, etc.
Cable type A
Cable structure Twisted, shielded twin-core cable
Wire cross-section
0.8 mm
2
(AWG 18)
Loop resistance (direct
current)
44 Ω/km
Characteristic impedance
at 31.25 kHz
100 Ω ±20%
Attenuation constant at
39.0 kHz
3 dB/km
Capacitive asymmetry 2 nF/km
Envelope delay distortion
(7.9 to 39 kHz)
1.7 ms/km
Shield coverage 90 %
The following are examples of suitable cable types:
Non-hazardous area:
Siemens 6XV1 830-5BH10
Belden 3076F
Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL