Proline Prowirl R 200 HART Commissioning
Endress+Hauser 123
Diagnostic event category
→ 124
Diagnostic event simulation
→ 124
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Assign simulation process variable – Select a process variable for
the simulation process that is
activated.
• Off
• Mass flow
• Flow velocity
• Volume flow
• Corrected volume
flow
• Temperature
• Calculated
saturated steam
pressure
*
• Total mass flow
*
• Condensate mass
flow
*
• Energy flow
• Heat flow
difference
*
• Reynolds number
Off
Process variable value In the Assign simulation
process variable parameter
(→ 123), one of the
following options is selected:
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
*
• Pressure
• Calculated saturated steam
pressure
*
• Total mass flow
*
• Condensate mass flow
*
• Energy flow
*
• Heat flow difference
*
• Reynolds number
*
Enter the simulation value for
the selected process variable.
Depends on the
process variable
selected
0
Current input 1 simulation – Switch simulation of the
current input on and off.
• Off
• On
Off
Value current input 1 In the Current input
simulation parameter, the On
option is selected.
Enter the current value for
simulation.
3.59 to 22.5 mA 3.59 mA
Current output 1 to n simulation – Switch the simulation of the
current output on and off.
• Off
• On
Off
Value current output 1 to n In the Current output 1 to n
simulation parameter, the On
option is selected.
Enter the current value for
simulation.
3.59 to 22.5 mA 3.59 mA
Frequency output simulation In the Operating mode
parameter, the Frequency
option is selected.
Switch the simulation of the
frequency output on and off.
• Off
• On
Off
Frequency value In the Frequency output
simulation parameter, the On
option is selected.
Enter the frequency value for
the simulation.
0.0 to 1 250.0 Hz 0.0 Hz