Proline Prowirl R 200 HART Diagnostics and troubleshooting
Endress+Hauser 153
Options Description
Logbook entry only The device continues to measure. The diagnostic message is displayed only in the Event
logbook submenu (Event list submenu) and is not displayed in alternation with the
operational display.
Off The diagnostic event is ignored, and no diagnostic message is generated or entered.
12.4.2 Adapting the status signal
Each item of diagnostic information is assigned a specific status signal at the factory. The
user can change this assignment for specific diagnostic information in the Diagnostic
event category submenu.
Expert → Communication → Diagnostic event category
Available status signals
Configuration as per HART 7 Specification (Condensed Status), in accordance with
NAMUR NE107.
Symbol Meaning
A0013956
Failure
A device error is present. The measured value is no longer valid.
A0013959
Function check
The device is in service mode (e.g. during a simulation).
A0013958
Out of specification
The device is being operated:
• Outside its technical specification limits (e.g. outside the process temperature range)
• Outside of the configuration carried out by the user (e.g. maximum flow in parameter
20 mA value)
A0013957
Maintenance required
Maintenance is required. The measured value is still valid.
A0023076
Has no effect on the condensed status.
12.5 Overview of diagnostic information
The amount of diagnostic information and the number of measured variables affected
increase if the measuring device has one or more application packages.
In the case of some items of diagnostic information, the status signal and the
diagnostic behavior can be changed. Change the diagnostic information → 152
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
Diagnostic of sensor
004 Sensor defective 1. Check plug connections
2. Change pre-amplifier
3. Change DSC sensor
F Alarm
022 Temperature sensor
defective
1. Check plug connections
2. Change pre-amplifier
3. Change DSC sensor
F Alarm
1)
046 Sensor limit exceeded 1. Check plug connections
2. Change pre-amplifier
3. Change DSC sensor
S Warning