Diagnostics and troubleshooting Proline Prowirl R 200 HART
154 Endress+Hauser
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
062 Sensor connection
defective
1. Check plug connections
2. Change pre-amplifier
3. Change DSC sensor
F Alarm
082 Data storage 1. Check module connections
2. Contact service
F Alarm
083 Memory content 1. Restart device
2. Restore S-Dat data
3. Change sensor
F Alarm
114 Sensor leaky Change DSC sensor F Alarm
122 Temperature sensor
defective
1. Check plug connections
2. Change pre-amplifier
3. Change DSC sensor
M Warning
1)
170 Pressure cell connection
defective
1. Check plug connections
2. Replace pressure cell
F Alarm
171 Ambient temperature
too low
Increase ambient temperature S Warning
172 Ambient temperature
too high
Reduce ambient temperature S Warning
173 Sensor range exceeded 1. Check process cond.
2. Increase system pressure
S Warning
174 Pressure cell electronics
defective
Replace pressure cell F Alarm
175 Pressure cell deactivated Enable pressure cell M Warning
Diagnostic of electronic
242 Software incompatible 1. Check software
2. Flash or change main electronics
module
F Alarm
252 Modules incompatible 1. Check if correct electronic modul
is plugged
2. Replace electronic module
F Alarm
261 Electronic modules 1. Restart device
2. Check electronic modules
3. Change I/O Modul or main
electronics
F Alarm
262 Module connection 1. Check module connections
2. Change electronic modules
F Alarm
270 Main electronic failure Change main electronic module F Alarm
271 Main electronic failure 1. Restart device
2. Change main electronic module
F Alarm
272 Main electronic failure 1. Restart device
2. Contact service
F Alarm
272 ECC settings faulty F Alarm
273 Main electronic failure 1. Emergency operation via display
2. Change main electronics
F Alarm
275 I/O module defective Change I/O module F Alarm
276 I/O module faulty 1. Restart device
2. Change I/O module
F Alarm
276 I/O module faulty F Alarm
277 Electronics defective 1. Change pre-amplifier
2. Change main electronic module
F Alarm
282 Data storage 1. Restart device
2. Contact service
F Alarm