Technical data Proline Prowirl R 200 HART
182 Endress+Hauser
Signal on alarm Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure mode Choose from:
4 to 20 mA in accordance with NAMUR recommendation NE 43
4 to 20 mA in accordance with US
Min. value: 3.59 mA
Max. value: 22.5 mA
Freely definable value between: 3.59 to 22.5 mA
Actual value
Last valid value
Pulse/frequency/switch output
Pulse output
Failure mode No pulses
Frequency output
Failure mode Choose from:
Actual value
0 Hz
Defined value: 0 to 1 250 Hz
Switch output
Failure mode Choose from:
Current status
Open
Closed
Local display
Plain text display With information on cause and remedial measures
Backlight Additionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
Via digital communication:
HART protocol
Via service interface
CDI service interface
Plain text display With information on cause and remedial measures
Load →  40
Low flow cut off The switch points for low flow cut off are preset and can be configured.
Galvanic isolation All inputs and outputs are galvanically isolated from one another.