Technical data Proline Prowirl R 200 HART
184 Endress+Hauser
Order code for "Sensor version; DSC sensor; measuring tube"
Increase in minimum
terminal voltage
Option DA:
Mass steam; 316L; 316L (integrated pressure/temperature measurement)
+ DC 1 V
Option DB:
Mass gas/liquid; 316L; 316L (integrated pressure/temperature
measurement)
+ DC 1 V
Power consumption Transmitter
Order code for "Output; input" Maximum power consumption
Option A: 4-20 mA HART 770 mW
Option B: 4-20 mA HART, pulse/
frequency/switch output
• Operation with output 1: 770 mW
• Operation with output 1 and 2: 2 770 mW
Option C: 4-20 mA HART + 4-20 mA
analog
• Operation with output 1: 660 mW
• Operation with output 1 and 2: 1 320 mW
Option D: 4-20 mA HART, pulse/
frequency/switch output, 4-20 mA current
input
• Operation with output 1: 770 mW
• Operation with output 1 and 2: 2770 mW
• Operation with output 1 and input: 840 mW
• Operation with output 1, 2 and input: 2840 mW
Current consumption Current output
For every 4-20 mA or 4-20 mA HART current output: 3.6 to 22.5 mA
If the option Defined value is selected in the Failure mode parameter :
3.59 to 22.5 mA
Current input
3.59 to 22.5 mA
Internal current limiting: max. 26 mA
Power supply failure • Totalizers stop at the last value measured.
• Configuration is retained in the device memory (HistoROM).
• Error messages (incl. total operated hours) are stored.
Electrical connection → 41
Potential equalization → 48
Terminals • For device version without integrated overvoltage protection: plug-in spring terminals
for wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
• For device version with integrated overvoltage protection: screw terminals for wire cross-
sections 0.2 to 2.5 mm
2
(24 to 14 AWG)
Cable entries • Cable gland: M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry:
– NPT ½"
– G ½"
Cable specification → 35