Proline Prowirl R 200 HART Technical data
Endress+Hauser 191
Shock resistance Shock, half-sine according to IEC 60068-2-27
• Order code for "Housing", option C "GT20 two-chamber, aluminum, coated, compact", J
"GT20 two-chamber, aluminum, coated, remote", K "GT18 two-chamber, 316L, remote"
6 ms, 50 g
• Order code for "Housing", option B "GT18 two-chamber, 316L, compact"
6 ms, 30 g
Impact resistance Rough handling shocks according to IEC 60068-2-31
Electromagnetic
compatibility (EMC)
As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
Details are provided in the Declaration of Conformity.
16.9 Process
Medium temperature range
DSC sensor
1)
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Medium temperature range
AA Volume; 316L; 316L –40 to +260 °C (–40 to +500 °F), stainless steel
AB Volume; Alloy C22; 316L
BA Volume high-temperature; 316L; 316L –200 to +400 °C (–328 to +752 °F), stainless steel
BB Volume high-temperature; Alloy C22; 316L
CA Mass; 316L; 316L –200 to +400 °C (–328 to +752 °F), stainless steel
CB Mass; Alloy C22; 316L
1) Capacitance sensor
Order code for "Sensor version; DSC sensor; measuring tube"
Option Description Medium temperature range
The "mass" sensor version (integrated pressure/temperature measurement) is available only for
measuring devices in the HART communication mode.
DA Mass steam; 316L; 316L –200 to +400 °C (–328 to +752 °F),
stainless steel
1) 2)
DB Mass gas/liquid; 316L; 316L –40 to +100 °C (–40 to +212 °F), stainless
steel
2)
1) Siphon enables use for extended temperature range (up to +400 °C (+752 °F)).
2) In steam applications, in conjunction with the siphon, the steam temperature may be higher (up to
+400 °C (+752 °F)) than the permitted temperature of the pressure measuring cell. Without a siphon, the
gas temperature is restricted due to the maximum permitted temperature of the pressure measuring cell.
This applies regardless of whether or not a stop cock is present.
Pressure measuring cell
Order code for "Pressure component"
Option Description Medium temperature range
B
C
D
E
Pressure measuring cell 2bar/29psi abs
Pressure measuring cell 4bar/58psi abs
Pressure measuring cell 10bar/145psi abs
Pressure measuring cell 40bar/580psi abs
–40 to +100 °C (–40 to +212 °F)