Installation Proline Prowirl R 200 HART
28 Endress+Hauser
Q
TT
1
2
3
A0019209
 9 Layout for delta heat measurement of saturated steam and water
1 Measuring device
2 Temperature sensor
3 Heat exchanger
Q Heat flow
Protective cover
Observe the following minimum head clearance: 222 mm (8.74 in)
For information on the weather protection cover, see →  169
6.2 Mounting the measuring device
6.2.1 Required tools
For transmitter
For turning the transmitter housing: Open-ended wrench8 mm
For opening the securing clamps: Allen key3 mm
For turning the transmitter housing: Open-ended wrench8 mm
For opening the securing clamps: Allen key3 mm
For sensor
For flanges and other process connections: Corresponding mounting tools
6.2.2 Preparing the measuring device
1. Remove all remaining transport packaging.
2. Remove any protective covers or protective caps present from the sensor.
3. Remove stick-on label on the electronics compartment cover.
6.2.3 Mounting the sensor
L
WARNING
Danger due to improper process sealing!
Ensure that the inside diameters of the gaskets are greater than or equal to that of the
process connections and piping.
Ensure that the gaskets are clean and undamaged.
Install the gaskets correctly.