Proline Prowirl R 200 HART Electrical connection
Endress+Hauser 39
+–
+ –
2
1
1
2
1 2 3 4
1 2 3 4
5
5
6
6
7
7
RDGNWHBN BK YE BU
+–
+ –
RES
VCC
GND
RES
VCC
GND
A0034571
13 Terminals for connection compartment in the transmitter wall holder and the sensor connection housing
1 Terminals for connecting cable
2 Grounding via the cable strain relief
Terminal number Assignment Cable color
Connecting cable
1 RS485 (-) DPC Brown
2 RS485 (+) DPC White
3 Reset Green
4 Supply voltage red
5 Grounding Black
6 RS485 (+) Yellow
7 RS485 (–) Blue
7.1.5 Requirements for the supply unit
Supply voltage
Transmitter
An external power supply is required for each output.
The following supply voltage values apply for the outputs available:
Supply voltage for a compact version without a local display
1)
Order code for "Output" Minimum
terminal voltage
2)
Maximum
terminal voltage
Option A: 4-20 mA HART ≥ DC 12 V DC 35 V
Option B: 4-20 mA HART, pulse/
frequency/switch output
≥ DC 12 V DC 35 V
Option C: 4-20 mA HART + 4-20 mA
analog
≥ DC 12 V DC 30 V
Option D: 4-20 mA HART, pulse/
frequency/switch output, 4-20 mA current
input
3)
≥ DC 12 V DC 35 V
1) In event of external supply voltage of the power supply unit with load
2) The minimum terminal voltage increases if local operation is used: see the following table
3) Voltage drop 2.2 to 3 V for 3.59 to 22 mA