Proline Prowirl R 200 HART Electrical connection
Endress+Hauser 47
Connecting cable (standard, reinforced)
8. Disconnect the signal cable from the connection board of the wall housing . by
pressing in the locking clip on the connector. Remove the transmitter housing.
9. Guide the connecting cable through the cable entry and into the connection housing
(if using a connecting cable without an M12 device plug, use the shorter stripped end
of the connecting cable).
10. Wire the connecting cable:
Terminal 1 = brown cable
Terminal 2 = white cable
Terminal 3 = yellow cable
Terminal 4 = green cable
11. Connect the cable shield via the cable strain relief.
12. Tighten the screws for the cable strain relief using a torque in the range of
1.2 to 1.7 Nm.
13. Reverse the removal procedure to reassemble the transmitter housing.
Connecting cable (option "mass pressure-/temperature-compensated")
8. Disconnect both signal cables from the connection board of the wall housing. by
pressing in the locking clip on the connector. Remove the transmitter housing.
9. Guide the connecting cable through the cable entry and into the connection housing
(if using a connecting cable without an M12 device plug, use the shorter stripped end
of the connecting cable).
10. Wire the connecting cable:
Terminal 1 = brown cable
Terminal 2 = white cable
Terminal 3 = green cable
Terminal 4 = red cable
Terminal 5 = black cable
Terminal 6 = yellow cable
Terminal 7 = blue cable
11. Connect the cable shield via the cable strain relief.
12. Tighten the screws for the cable strain relief using a torque in the range of
1.2 to 1.7 Nm.
13. Reverse the removal procedure to reassemble the transmitter housing.
7.2.3 Connecting the connecting cable for the pressure measuring
cell
When delivered to the customer, the connecting cable is connected as follows:
Compact version: to transmitter housing
Remote version: to sensor connection housing
For connection to sensor and pressure measuring cell:
Insert M12 plug of connecting cable into pressure measuring cell and screw into place.