System integration Proline Prowirl R 200 HART
72 Endress+Hauser
Parameter overview with brief description
Parameter Description Selection / User entry Factory setting
Burst mode 1 to n Activate the HART burst mode for burst
message X.
Off
On
Off
Burst command 1 to n Select the HART command that is sent to the
HART master.
Command 1
Command 2
Command 3
Command 9
Command 33
Command 48
Command 2
Burst variable 0 For HART command 9 and 33: select the
HART device variable or the process variable.
Volume flow
Corrected volume flow
Mass flow
Flow velocity
Temperature
Calculated saturated steam
pressure
*
Total mass flow
*
Energy flow
*
Heat flow difference
*
Condensate mass flow
*
Reynolds number
*
Totalizer 1
Totalizer 2
Totalizer 3
HART input
Density
*
Pressure
*
Specific volume
*
Degrees of superheat
*
Percent of range
Measured current
Primary variable (PV)
Secondary variable (SV)
Tertiary variable (TV)
Quaternary variable (QV)
Not used
Volume flow
Burst variable 1 For HART command 9 and 33: select the
HART device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 2 For HART command 9 and 33: select the
HART device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 3 For HART command 9 and 33: select the
HART device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 4 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 5 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 6 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 7 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst trigger mode Select the event that triggers burst message
X.
Continuous
Window
Rising
Falling
On change
Continuous
Burst trigger level Enter the burst trigger value.
Together with the option selected in the
Burst trigger mode parameter the burst
trigger value determines the time of burst
message X.
Signed floating-point number