Proline t-mass 65 Commissionin
g
Endress+Hauser 27
MODBUS RS485
Register 6859
Data type:
Integer
Register 6821
Data type:
String (18 byte)
No. Error message / Type Cause/remedy
19 SENSOR DEFECT 070 S: SENSOR DEFECT
$: # 070
Flow sensors are likely to be defect, measurement
is no longer possible.
Please contact your Endress+Hauser sales
organization.
30 COMMUNIC.AMP. 251 S: COMMUNIC. SENS
$: # 251
Internal microprocessor communication fault on
the amplifier board. Remove the amplifier board.
→ Operating Instructions on CD-ROM
59 FLOW LIMIT 422 P: FLOW LIMIT
$: # 422
The measured flow has exceeded the maximum
limit.
Reduce the flow rate or replace the instrument
with a suitable size for the application.
!
Note!
Error can be configured as a fault or notice
message.