Installation Proline t-mass 65 PROFIBUS DP/PA
16 Endress+Hauser
Outlet runs with pressure measuring points
The pressure measuring point should be installed downstream of the measuring device, so that there
is no potential influence of the pressure transmitter process connection on the flow entering the
measuring point.
a0005114
Fig. 5: Installing a pressure measuring point (PT = pressure transmitter)
Perforated plate flow conditioner
It is recommended to install a perforated plate flow conditioner if the recommended inlet runs are
not available. See accessories ä 87.
a0005115
Fig. 6: The figure above illustrates the minimum recommended inlet and outlet runs expressed in multiples of the pipe
diameter using a flow conditioner.
1 = Flow conditioner with the flanged sensor, 2 = Flow conditioner with the insertion sensor
Flow conditioner for use with insertion sensors
The well known "Mitsubishi" design is recommended for this application DN 80 mm (3") to
DN 300 mm (12"). The flow conditioner must be installed at a distance of 8 × DN upstream of the
sensor. A further 5 pipe diameters inlet run is required upstream of the actual conditioner itself.
PT
2...5xDN
2 × DN5 × DN
8 × DN 5 × DN
5 × DN
2
1