Proline t-mass 65 PROFIBUS DP/PA Wiring
Endress+Hauser 27
4 Wiring
#
Warning!
When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to
these Operating Instructions. Please do not hesitate to contact your Endress+Hauser representative
if you have any questions.
!
Note!
The device does not have an internal power isolation switch. Therefore provide an isolation switch
or circuit breaker which can be used to disconnect the power supply to the device.
4.1 Cable specifications
4.1.1 PROFIBUS DP cable specifications
Cable type
Two versions of the bus line are specified in IEC 61158. Cable type A can be used for all
transmission rates up to 12 Mbit/s.
Bus structure
Note the following points:
The maximum line length (segment length) depends on the transmission rate.
For cable type A, the maximum line length (segment length) is as follows:
A maximum of 32 users are permitted per segment.
Each segment is terminated at either end with a terminating resistor.
The bus length or the number of users can be increased by introducing a repeater.
The first and last segment can comprise max. 31 devices.
The segments between the repeaters can comprise max. 30 stations.
The maximum distance between two bus users can be calculated as follows:
(NO_REP + 1) × segment length
!
Note!
NO_REP = maximum number of repeaters that may be switched in series depending on the
repeater in question.
Example
In accordance with manufacturer specifications, 9 repeaters can be switched in series when using
a standard line. The maximum distance between two bus users at a transmission rate of
1.5 MBit/s can be calculated as follows: (9 + 1) × 200 m = 2000 m
Cable type A
Characteristic impedance 135 to 165 at a measuring frequency of 3 to 20 MHz
Cable capacitance < 30 pF/m
Core cross-section > 0.34 mm
, corresponds to AWG 22
Cable type Twisted in pairs, 1 × 2, 2 × 2 or 1 × 4 wire
Loop-resistance 110 /km
Signal damping Max. 9 dB over the entire length of the cable section
Shielding Copper braided shielding or braided shielding and foil shielding
Transmission rate [kBit/s] 9.6 to 93.75 187.5 500 1500 3000 to 12000
Line length [m]([inch]) 1200 (4000) 1000 (3300) 400 (1300) 200 (650) 100 (330)