Proline t-mass 65 PROFIBUS DP/PA Commissioning
Endress+Hauser 71
6.6.4 Configuration examples with Simatic S7 HW-Konfig
Example 1
a0005497
Fig. 39: Complete configuration using the t-mass 65 GSD file
It is essential to adhere to the following sequence when configuring the modules in the
PROFIBUS Master (class 1):
Slot
sequence
Module
Byte
length
input
data
Byte
length
output
data
Description
1AI5-
Analog Input function block 1
Output variable mass flow (factory setting)
2AI5-
Analog Input function block 1
Output variable corr. volume flow (factory setting)
3AI5-
Analog Input function block 1
Output variable temperature (factory setting)
4
SETTOT
_MODETOT
_TOTAL
52
Totalizer function block 1
TOTAL output variable = totalized mass flow (factory setting)
SETTOT totalizer control
MODETOT totalizer configuration
5
SETTOT
_MODETOT
_TOTAL
52
Totalizer function block 2
TOTAL output variable = totalized mass flow (factory setting)
SETTOT totalizer control
MODETOT totalizer configuration
6
DISPLAY
_VALUE
-5
Value for local display
7
CONTROL
_BLOCK
-1
Control of device functions
8
PRESSURE
_VALUE
-5
Process pressure