Proline t-mass 65 Hardware settings
Endress+Hauser
19
PROFIBUS
MODBUS RS485
A0007552
Device address range: 0 to 126
Factory setting: 126
a. Miniature switches for the device address
(example shown: 1+16+32 = device address 49)
b. Miniature switches for the addressing mode:
OFF = software addressing via local
operation/operating program (factory setting)
ON = hardware addressing via miniature switches
c. Miniature switch not assigned.
A0007554
Device address range: 1 to 247
Factory setting: 247
a. Miniature switches for the device address
(example shown: 1+16+32 = device address 49)
b. Miniature switches for the addressing mode:
OFF = software addressing via local
operation/operating program (factory setting)
ON = hardware addressing via miniature switches
c. Miniature switch not assigned.
161
3
322
4
643
4
1
2
b
OFF ON
11
22
43
84
a
OFF ON
c
161
3
322
4
643
1284
1
2
b
OFF ON
11
22
43
84
a
OFF ON
c