6 Commissioning Promag 53 PROFIBUS-DP/-PA
100 Endress+Hauser
Example 2:
Replacing measured variables with placeholders (EMPTY_MODULE) using the manu-
facturer-specific GSD file:
This form of configuration activates the volume flow, totalizer 1, display value and the
manufacturer-specific control blocks.
Totalizer 1 is configured without control variable. In this example it provides a meas-
ured value and cannot be controlled. It is not possible to reset or stop the totalizer.
Configuration data
Byte
length
(Input)
Byte
length
(Out-
put)
Data
blocks
Status Access
type
GSD
block
designation
GSD
Extended
block
identifica-
tion
GSD
Standard
block
identifica-
tion
0...4 Volume
flow +
Status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
5...9 Totalizer 1
+ Status
active read TOTAL. 0x41, 0x84,
0x85
0x41, 0x84,
0x85
––Place-
holder
disa-
bled
EMTPY_
MODULE
0x00 0x00
––Place-
holder
disa-
bled
EMTPY_
MODULE
0x00 0x00
––Place-
holder
disa-
bled
EMTPY_
MODULE
0x00 0x00
0...4 Display
value
active write DISPLAY_
VALUE
0x82, 0x84,
0x08, 0x05
0xA4
5 Control
variable
active write CONTROL_
BLOCK
0x20 0x20
Slot 0: AI volume flow
Slot 1: Totalizer 1 without control variable
Slot 2: Placeholder (EMPTY_MODULE)
Slot 3: Placeholder (EMPTY_MODULE)
Slot 4: Placeholder (EMPTY_MODULE)
Slot 5: Display value (DISPLAY_VALUE)
Slot 6: Control block (CONTROL_BLOCK) manufacturer-specific
F06-53PBxxxx-20-xx-xx-xx-002