Remote Operation
Handheld Terminal
Operating the Prosonic transmitter is
even easier if it is connected via a serial
interface. All values can then be entered
using a handheld terminal. The user has
comprehensive and detailed information
on inputs both on-site and in the control
room. The measurement remains totally
unaffected during the interactive input.
Two different handheld terminals are
available:
Commulog VU 260 Z is used with the
serial interface for the INTENSOR
protocol. It can be connected to all
Endress+Hauser instruments with an
INTENSOR protocol.
Universal HART communicator via the
serial interface with the HART protocol
(Type C).
Electrical Connection
A minimum resistance must be present
in the circuit for correct transmission of
the communications signal to take place
(see Technical Data).
The handheld terminal is connected
either
directly to current output 1 of the
transmitter or
to a communications resistor.
In general: The handheld terminal can
be connected anywhere in the signal
circuit as long as there is a resistance
between its terminals which is larger
than the minimum communications
resistor.
Technical Data
Maximum load: 600
Communications resistor: 250
Screened cable recommended,
maximum capacitance 100 nF.
Operation via Commuwin II
The Commubox FXA 191 connects
intrinsically safe Smart transmitters that
have an INTENSOR- or HART protocol
to the RS 232 C serial interface of a
personal computer. This enables the
transmitter to be remotely operated with
the Endress+Hauser Commuwin II
operating program.
-
I-
45
I+
Field
Control room
4…20 mA
Communication
resistor
Connection of handheld
terminals Commulog
VU 260 Z (INTENSOR)
and Universal HART
Communicator
DXR 271 (HART) in the
field and in the control
room.
-
VH
Commuwin II
Commubox
optional
power pack
4…20 mA
minimum total resistance 250
RS 232 C
Connecting the
Commubox
5