Installation Prosonic M - FOUNDATION Fieldbus
22 Endress+Hauser
3.3.3 Installation conditions for flow measurements
Install the Prosonic M at the inflow side, as close above the maximum water level H
max
as possible
(take into account the blocking distance BD).
Position the Prosonic M in the middle of the channel or weir.
Align the sensor membrane parallel to the water surface.
Keep to the installation distance of the channel or weir.
You can enter the "Flow to Level" linearisation curve ("Q/h curve") using the operating program
or manually via the on-site display.
Example: Khafagi-Venturi flume
L00-FMU4xxxx-17-00-00-xx-003
A Khafagi-Venturi flume
BInflow
C Outflow
BD Blocking distance
E Empty calibration
F Full calibration
V Direction of flow
1xb
0
b
0
BD
A
E
BC
V
H
max
=F