Installation Prosonic M - FOUNDATION Fieldbus
26 Endress+Hauser
3.6 Turn housing
After mounting, the housing can be turned 350° in order to simplify access to the display and the
terminal compartment. Proceed as follows to turn the housing to the required position:
• Undo the fixing screws (allen key 4 mm (0.16 in))
• Turn the housing in the required direction
• Tighten up the fixing screws. Maximum torque 0.5 Nm (0.36 lbf ft).
• Loctite can be used for securing the screw.
L00-FMU4xxxx-17-00-00-yy-013
A Housing F12
B Housing T12
3.7 Post installation check
After installing the device, carry out the following checks:
• Is the device damaged (visual inspection)?
• Does the device correspond to the measuring point specifications for process temperature, process
pressure, ambient temperature, measuring range etc.
• If available: Are the measuring point number and labelling correct (visual inspection)?
• Is the measuring device sufficiently protected against precipitation and direct sunlight?
• Are the cable glands tightened correctly?
• After aligning the housing, check the process seal at the nozzle or flange.