Installation Prosonic M - FOUNDATION Fieldbus
26 Endress+Hauser
3.6 Turn housing
After mounting, the housing can be turned 350° in order to simplify access to the display and the
terminal compartment. Proceed as follows to turn the housing to the required position:
Undo the fixing screws (allen key 4 mm (0.16 in))
Turn the housing in the required direction
Tighten up the fixing screws. Maximum torque 0.5 Nm (0.36 lbf ft).
Loctite can be used for securing the screw.
L00-FMU4xxxx-17-00-00-yy-013
A Housing F12
B Housing T12
3.7 Post installation check
After installing the device, carry out the following checks:
Is the device damaged (visual inspection)?
Does the device correspond to the measuring point specifications for process temperature, process
pressure, ambient temperature, measuring range etc.
If available: Are the measuring point number and labelling correct (visual inspection)?
Is the measuring device sufficiently protected against precipitation and direct sunlight?
Are the cable glands tightened correctly?
After aligning the housing, check the process seal at the nozzle or flange.