Wiring Prosonic M - FOUNDATION Fieldbus
30 Endress+Hauser
4.5 Recommended connection
L00-FMU4xxxx-17-00-00-yy-014
1 External ground terminal of the transmitter
For maximum EMC protection please observe the following points:
As the metal housing of the Prosonic M is isolated from the tank by the plastic sensor, a low-
impedance connection between the housing and tank/bracket/flange should be installed in order
to ensure electromagnetic compatibility (EMC).
For optimum EMC the connection should be as short as possible. Ideally, a ground strap should
be used.
The continuity of the cable screening between tapping points must be ensured.
If potential equalisation is present between the individual grounding points, ground the screening
at each cable end or connect it to the device housing (as short as possible).
If there are large differences in potential between grounding points, the grounding should run via
a capacitor that is suitable for high frequency use (e.g. ceramic 10 nF/250 V&).
"
Caution!
Applications, which are subject to the explosion prevention, permit only under special conditions
the repeated grounding of the protective screen , see to EN 60 079-14..
4.6 Post connection check
After wiring the device, carry out the following checks:
Are the terminals correctly assigned?
Is the cable gland tight?
If available: Is the FOUNDATION Fieldbus connector screwed tight?
Is the housing cover fully screwed on?
If power supply available: Does a display appear on the display module?