Prosonic M - FOUNDATION Fieldbus Commissioning
Endress+Hauser 45
6.4.2 Basic setup
The "Basic setup" (00) function group lists all the functions which are required for a standard
measurement task to commission the Prosonic M. When you have completed your input for a
function, the next function appears automatically. In this way, you are guided through the complete
calibration.
L00-FMU4xxx-19-00-00-en-000
D Distance (distance from the sensor membrane (= reference point of the measurement) / product)
E Empty calibr. (= zero point
F Full calibr. (= span)
LLevel
BD Block distance
SD Safety distance
20 mA
100%
4mA
0%
D
L
F
E
BD
SD
tank shape
dome ceiling
medium property
Unknown
process cond.
Standard
safety settings
linearisation
extended calibr.
...
empty calibr.
full calibr.
option
Interference echo
suppression
(tank mapping)