Technical Data Prosonic M - FOUNDATION Fieldbus
80 Endress+Hauser
10.1.6 Ambient conditions
Ambient temperature -40 °C to +80 °C (-40 °F to +176 °F)
The functionality of the LC display becomes restricted at Tu<-20 °C (Tu<-4 °F) and Tu>+60 °C
(Tu>+140 °F).
If the device is operated outdoors in strong sunlight, you should use a protective cover.
Storage temperature -40 °C to +80 °C (-40 °F to +176 °F)
Climate class DIN EN 60068-2-38 (Test Z/AD) DIN/IEC 68 T2-30Db
Ingress protection • With closed housing, tested according to
– IP 68, NEMA 6P (24h at 1.83 m (6 ft) under water surface)
– IP 66, NEMA 4x
• With open housing: IP 20, NEMA 1 (also ingress protection of the display)
Vibration resistance DIN EN 60068-2-64 / IEC 68-2-64: 20…2000 Hz, 1 (m/s
)
2
/Hz; 3 x 100 min
Electromagnetic compatibility
(EMC)
• Electromagnetic compatibility according to all relevant requirements of the EN 61326- series and
NAMUR recommendation EMC (NE21). For details see declaration of conformity.
10.1.7 Process conditions
Process temperature -40°C to +80°C (-40 °F to +176 °F)
A temperature sensor is integrated in the sensor for correction of the temperature-dependent time-
of-flight.
Process pressure • FMU40, FMU41: 0.7 bar to 3bar abs. (10.15 psi to 43.5 psi abs.)
• FMU42, FMU43, FMU44: 0.7 bar to 2.5bar abs. (10.15 psi to 36.25 psi abs.)