2.7 Installation check
After installing the device, carry out the following checks:
• Is the device damaged (visual inspection)?
• Does the device correspond to the measuring point specifications for process temperature,
process pressure, ambient temperature, measuring range etc.
• If available: Are the measuring point number and labelling correct (visual inspection)?
• Is the measuring device sufficiently protected against precipitation and direct sunlight?
• Are the cable glands tightened correctly?
• After aligning the housing, check the process seal at the nozzle or flange.
1
1
2
2
F12 housing T12 housing
allen key
4 mm/0.1”
max. torque
0.5 Nm (0.36 lbf ft)