EasyManua.ls Logo

Endress+Hauser Prosonic M FMU41 - Product structure FMU40

Endress+Hauser Prosonic M FMU41
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Prosonic M FOUNDATION Fieldbus Mounting
Endress+Hauser 7
2.3 Installation conditions
2.3.1 Installation conditions for level measurements
L00-FMU4xxxx-17-00-00-de-005
Do not install the sensor in the middle of the tank (3). We recommend leaving a distance
between the sensor and the tank wall (1) measuring 1/3 of the tank diameter.
Use a protective cover, in order to protect the device from direct sun or rain (2).
Avoid measurements through the filling curtain (4).
Make sure that equipment (5) such as limit switches, temperature sensors, etc. are not located
within the emitting angle α. In particular, symmetrical equipment (6) such as heating coils,
baffles etc. can influence measurement.
Align the sensor so that it is vertical to the product surface (7).
Never install two ultrasonic measuring devices in a tank, as the two signals may affect each
other.
To estimate the detection range, use the 3 dB emitting angle α.
Sensor α L
max
r
max
FMU40 11° 5 m (16 ft) 0.48 m (1.6 ft)
FMU41 11° 8 m (26 ft) 0.77 m (2.5 ft)
FMU42 10 m (33 ft) 0.79 m (2.6 ft)
FMU43 15 m (49 ft) 0.79 m (2.6 ft)
FMU44 11 ° 20 m (66 ft) 1.93 m (6.3 ft)
1
234
5
6
1/3D
7
D
r
a
L

Other manuals for Endress+Hauser Prosonic M FMU41

Related product manuals