Mounting Prosonic M FOUNDATION Fieldbus
8 Endress+Hauser
2.3.2 Installation in narrow shafts
2.3.3 Installation conditions for flow measurements
Install the Prosonic M at the inflow side, as close above the maximum water level H
max
as
possible (take into account the blocking distance BD).
Position the Prosonic M in the middle of the channel or weir.
Align the sensor membrane parallel to the water surface.
Keep to the installation distance of the channel or weir.
You can enter the "Flow to Level" linearisation curve ("Q/h curve") using operating program
FieldCare or manually via the on-site display.
Example: Khafagi-Venturi flume
L00-FMU4KAxx-17-00-00-en-003
In narrow shafts with strong interfe-
rence echoes, we recommend using an
ultrasound guide pipe (e.g. PE or PVC
wastewater pipe) with a minimum dia-
meter of 100 mm (3.94 in).
Make sure that the pipe is not soiled by
accumulated dirt. If necessary, clean
the pipe at regular intervals.
L00-FMU4xxxx-17-00-00-en-010
ENDRESS+HAUSER
Prosonic M
ENDRESS+HAUSER
Prosonic M
ENDRESS+HAUSER
Prosonic M
ENDRESS+HAUSER
Prosonic M
venting
hole
1xb
0
b
0
BD
Khafagi - Venturi - flume
direction of flow
inflow
outflow
empty calibr.