Technical Data Prosonic M - FOUNDATION Fieldbus
78 Endress+Hauser
10.1.4 Power supply
Terminals Cable cross-section: 0.5 to 2.5 mm (20 to 14 AWG)
Cable entry • Cable gland M20x1.5 (recommended cable diameter 6 to 10 mm (0.24 to 0.39 in))
• Cable entry G½ or ½ NPT
• 7/8" FOUNDATION Fieldbus plug
Supply voltage 9 V to 32 V
There may be additional restrictions for devices with an explosion protection certificate. Refer to the
notes in the appropriate safety instructions (XA).
Lift-off voltage 9 V
Basic current 15 mA
In-rush current 15 mA
Error current 0 mA
FISCO
FNICO compliant yes
Polarity sensitive no
Integrator Block The Integrator Function Block integrates a variable as a
function of the time or accumulates the counts from a
Pulse Input block. The block may be used as a totalizer
that counts up until reset or as a batch totalizer that has a
setpoint, where the integrated or accumulated value is
compared to pre-trip and trip settings, generating discrete
signals when these settings are reached.
60 ms standard
Block Content Execution time Functionality
U
i
17,5 V
I
i
500 mA; with surge arrester 273 mA
P
i
5,5 W; with surge arrester1, 2 W
C
i
5 mF
L
i
0,01 mH