The "relays/controls" menu
101
"pump M/control N" (M = 1 - 6; N = 1 or 2)
(Part 1: Switching points for limit control)
"switch on point"
Specifies the switch-on point of the respective pump. Use the selected level unit.
"
Caution!
After a change of the "unit level" the switch-on point has to be checked and adjusted if required.
"switch off point"
Specifies the switch-off point of the respective pump. Use the selected level unit.
"
Caution!
After a change of the "unit level" the switch-off point has to be checked and adjusted if required.
"switch-on delay"
Specifies the switch-on delay of the respective pump (in seconds).
When the level has risen above the switch-on point, the relay does not switch immediately but only
after the specified switch-on delay. Assign different delays to the individual pumps in order to avoid
simultaneous switching-on of several pumps (which could cause an overload of the power supply
system).
L00-FMU90xxx-19-00-00-yy-055
A: switch-on point; B: switch-off point; C: pump on; D: pump off; E: switch-on delay
⇒
pump 1/control 1 R1303
switch on point:
switch off point:
switch on delay:
crust reduction:
t
t
A
B
C
D
E