The "relays/controls" menu
105
"relay allocation"
Allocates a relay to the pump.
Selection:
All relays of the instrument version at hand
"relay N" (N = 1 - 6)
"function"
Allocates the desired function to the relay.
Selection:
none (default)
•pump M/control N
!
Note!
If a standby pump has been parametrized: The standby pump is always the last of the pumps.
Therefore, during the relay allocation the last pump must be selected in the "function" parameter.
Example:
number of pumps: 5
stand by pump: yes
=> for the standby pump: "function" = pump 5/control N
"invert"
Determines if the switching behavior of the relay is inverted.
Selection:
no (default)
The switching behavior of the relay is not inverted. The relay is energized if the pump should be
switched on.
yes
The switching behavior of the relay is inverted. The relay is energized if the pump should be
switched off.
relay allocation RN305
relay 1
relay 2
relay 3
relay 4
relay N RN306
function:
invert: