The "relays/controls" menu
110
5.3.5 The "flush control" submenu
The flush control is used to switch a pump on for a number of cycles (flush cycles) for a defined time
(flush time). This switching-on takes place within the defined number of pump cycles. The figure
below shows an example with 5 pump cycles and 2 flush cycles. The last two of the five pump cycles
are used for flushing.
A pump cycle always starts with the first pump being switched on and ends if all pumps are switched
off again.
L00-FMU90xxx-19-00-00-yy-109
A: 5 pump cycles; B: 2 flush cycles; C: flush delay; D: flush time
"flush control N" ( N = 1 or 2)
"flush control"
Use this parameter to switch the flush control on and off.
Selection:
• off (default)
•on
"pump cycles"
Defines the number of pump cycles after which the flush cycles are started.
Default: 0
"flush cycles"
Defines the number of flush cycles within the number of pump cycles.
Default: 0
!
Note!
The number of flush cycles must be eqal or less than the number of pump cycles.
"flush time"
Defines, how long the flush relay is switched on.
Default: 0 s
"flush delay"
Defines the interval between the start of the pump cycle and the start of the flush relay.
Default: 0 s
t
132451
C D
12
A
B
⇒
flush control 1 R1603
flush control:
pump cycles:
flush cycles:
flush time: