The "relays/controls" menu
117
!
Note!
The alarm is deactivated by a reset of the operating hours in the "pump data" submenu (e.g. after
the maintenance of the pump has been completed).
"relay allocation"
Defines a relay which is associated with the operating hours alarm.
Selection:
All relays of the instrument version at hand.
!
Note!
The relay is not allocated to a specific pump. It only indicates that the operating hours alarm is active
for one of the pumps. At the same time an error message is generated which states the number of
the affected pump.
"relay N" (N = 1 - 6)
"function"
Allocates the desired function to the relay.
Selection:
none (default)
Operating hours alarm N (N = 1 or 2)
"invert"
Determines if the switching behavior of the relay is inverted.
Selection:
no (default)
The switching behavior of the relay is not inverted. The relay is de-energized if an operating hours
alarm is active.
yes
The switching behavior of the relay is inverted. The relay is energized if an operating hours alarm
is active.
relay allocation RX614
relay 1
relay 2
relay 3
relay 4
relay N RN615
function:
invert: