The "relays/controls" menu
123
Selection:
• actual value (default)
The relay switches according to the current measuring value (although its reliability is not
ensured).
• hold
The current switching state of the relay is held.
• switch on
The relay is energized.
• switch off
The relay is de-energized.
5.4.6 "relay allocation"
Allocates a relay to the rake control function.
Selection:
• All relays of the instrument version at hand.
5.4.7 "relay N" (N = 1 ... 6)
"function" parameter
The relay function is defined by this parameter.
Selection:
• none (default)
• rake control
"invert" parameter
In this parameter, specify if the switching behaviour of the relay is to be inverted.
Selection:
• no (default)
The switching behaviour of the relay is not inverted. The relay is energized if the rake cleaning
should be active.
• yes
The switching behaviour of the relay is inverted. The relay is energized if the rake cleaning should
be inactive.
⇒
relay allocation RX203
relay 1
relay 2
relay 3
relay 4
⇒
relay 2 R2306
function:
invert: