The "level" menu
36
2.3 The "simulation" submenu
2.3.1 "LVL N simulation" (N = 1 or 2)
"simulation"
"sim. level value"
This parameter is available for a level simulation. It is used to specify the desired level value. The
display and the output signal assume values according to this level.
"sim. vol. value"
This parameter is available for a volume simulation (more general: a simulation of the linearized
value). It is used to specify the desired volume (or linearized value). The output signal assumes a
value according to this volume.
⇒
LVL1 Simulation L1022
simulation:
(sim. level value:)
(sim. vol. value:)
The parameters of this set are used to simulate a level or a measured
value in order to check the linearisation, the signal output and the
connected switching units.
L00-FMU90xxx-19-00-00-yy-020
(1): simulation of level; (2): simulation of volume
Use this parameter to select the simulation
mode:
• sim off.
This is the normal mode used for
measurement. No simulation is performed in
this mode.
• sim. level
After selection of this mode, the "sim. level
value" parameter appears, where you can
specify a level value (1). The display and the
output signal assume values according to this
level.
Use this mode to check the linearisation.
• sim. volume
After selection of this mode, the "siml vol.
value" parameter appears, where you can
specify a volume value (2). The output
assumes a value according to this volume.
Use this mode to check the signal output and
the connected switching units.
!
Note!
An error mesage is generated as long as one of
the modes "sim. level" or "sim. volume" is
active.
(1) (2)
0/4...2