The "flow" menu
40
• read:
The table editor appears. An existing table can be viewed but not changed.
• manual:
The table editor appears. Table values can be entered and changed.
• delete:
The linearization table is deleted.
The table editor
L00-FMU90xxx-19-00-00-de-006
"status"
Use this parameter to specify if the linearization table is to be used or not.
Selection:
• enabled
The table is used.
• disabled
The table is not used. A flow value is not calculated.
"alpha", "beta", "gamma" and "C"
These parameters are available for the "formula" linearization type.
They are used to specify the parameters of the flow formula:
Q = C(h
α
+ γh
β
)
"max flow"
This parameter is available for the linearization types "flume/weir" and "formula".
It is used to specify the maximum flow of the respective weir or flume.
For each of the preprogrammed curves, a default value is preset. However, this value can be
adjusted, e.g. if the weir/flume is applied for lower flows.
The maximum flow corresponds to an output current of 20 mA.
No.
Level
Value
1
0,0000
0,0000
2
0,0000
0,0000
3
0,0000
0,0000
…
0,0000
0,0000
: go to next row
: go to previous row
: open marked row
for editing
No.
Level
Value
1
0,0000
0,0000
2
0,0000
0,0000
3
0,0000
0,0000
…
0,0000
0,0000
: navigate within the table
: (for "Level" und "Value”)
open marked number
for editing
: (for "No.")
open row editor
Row function
(before current row)
Query: new position
Return to the previous
step by this
key combination.
- Delete row
- Insert row
- Move row