The "flow" menu
42
"flow N" (N = 1 or 2)
"flow N" (N = 1 or 2)
Displays the currently measured flow Q.
If the displayed value does not match the real flow, it is recommended to check the linearisation.
"level"
Displays the currently measured level L.
If the displayed value does not match the real level, it is recommended to check the empty
calibration.
"sensor"
Displays the currently measured distance D between the sensor membrane and the liquid surface.
If the displayed value does not match the real distance, it is recommended to perform an
interference echo suppression.
FDU95 - *2*** (high temperature version) 0,9 m 45 m (for solids)
FDU96 1,6 m 70 m (for solids)
FDU80/FDU80F 0,3 m 5 m (for liquids)
FDU81/81F 0,5 m 10 m (for liquids)
FDU82 0,8 m 20 m (for liquids)
FDU83 1 m 25 m (for liquids)
FDU84 0,8 m 25 m (for solids)
FDU85 0,8 m 45 m (for solids)
FDU86 1,6 m 70 m (for solids)
1) valid for optimum process conditions
Type of sensor blocking distance (BD) maximum measuring dis-
tance
1)
⇒
flow 1 F1005
flow 1:
level:
sensor: