46
3.1.2 The "extended calibration" submenu
"flow N mapping" (N = 1 or 2)
Is identical to the "flow N mapping" parameter set in the "basic setup" submenu, see page 44.
"flow N low cut off" (N = 1 or 2)
"low flow cut off"
Use this function to enter a lower limit for the flow (percentage of the "maximum flow"). If the flow
falls below this cut off limit, it is not taken into account for the flow counters (which are paramet-
rized in the "flow counter" submenu, see below).
"flow N" (N = 1 or 2)
Displays the currently measured flow.
"flow N distance correction"
"correction"
This parameter can be used to shift the measured distance (from the sensor membrane to the water
surface) by a constant value. The distance entered into this parameter is added to the measured dis-
tance.
"flow N" (N = 1 or 2)
Displays the currently measured flow in order to show the influence of the distance correction on
the flow.
flow 1 mapping F1010
sensor:
range of mapping:
start mapping:
status:
flow1 low cut off F1011
low flow cut off:
flow 1:
flow 1 dist. corr. F1012
correction:
flow1: