The "safety settings" menu
65
4 The "safety settings" menu
4.1 "output on alarm" (only for HART instruments)
4.1.1 "output N" (N = 1 or 2) (only for HART instruments)
Defines the output current in the case of an alarm.
Selection:
min (3.6 mA)
max (22 mA) (Default)
user specific (as defined in the "output value N" parameter)
hold (the last value is held)
L00-FMU90xxx-19-00-00-yy-069
A: min.; B: max.; C: user specific; D: hold; E: output value
4.1.2 "oputput value N" (N = 1 or 2) (only for HART instruments)
Defines the output current in the case of an alarm.
(only available for "output N" = "user specific")
range of values: 3.6 ... 22 mA
main menu CX001
safety settings
relay/controls
output/calculat
device properties
output on alarm AX101
output 1:
output value 1:
output 2:
output value 2:
t
t
t
[mA]
[mA]
[mA]
22
22
22
3.6
3.6
3.6
t
[mA]
22
3.6
A
B
D
C
E