The "relays/controls" menu
80
5.1.11 "relay N (N = 1 - 6)"
(Relay behavior)
"switch delay" (only available for limit relays)
Use this parameter to specify the switch delay (in seconds).
The relay does not switch immediately after the switch-on point has been exceeded but only after
the specified delay.
The measured value must exceed the switch-on point during the entire delay time.
"invert"
Use this parameter to specify if the switching direction of the relay is to be inverted.
Selection:
no (default)
The switching direction of the relay is not inverted. The relay switches as described in the above
sections.
yes
The switching direction of the relay is inverted. The states "energized" and "de-energized" are
interchanged.
"error handling" (not available for alarm and diagnostic relays)
Use this parameter to specify the reaction of the relay in the case of an error.
Selection:
actual value
The relay switches according the the currently measured value (although its reliability is not
ensured).
hold (default)
Limit relay: The current switching state of the relay is maintained.
Counting pulse relay: The counter uses the flow value which was present when the error
occurred.
switch on
(only available for limit relays)
The relay is energized.
switch off
(only available for limit relays)
The relay is de-energized.
stop
(only available for counting pulse and time pulse relays)
No pulses are generated as long as the error is present.
relay X RX104
switch delay:
invert:
error handling: