Commissioning Prosonic S FMU90 Flow Measurement PROFIBUS
40 Endress+Hauser
9 → Flow N state
(N = 1 or 2)
→ Level Displays the currently measured level
→ Distance Displays the currently measured distance between the
reference point of the sensor and the liquid surface. Check
the value:
•Value correct: → Basic calibration completed.
Press several times to return to the measured value
display.
• Value incorrect: → go back to step 7 ("flow N check
value")
Flow N
(N = 1 or 2)
Displays the currently measured flow
Status Used to enable, disable or delete a mapping
10 Parametrization of the counters
(in the operating menu: "flow/flowcounter")
1) The type of linearization determines the relationship between the measured level and the flow.
Step Parameter Set Parameter Remarks