Commissioning Prosonic S FMU90 Flow Measurement PROFIBUS
46 Endress+Hauser
9 LVL 1(2) state Level 1(2) Indicates the currently measured level.
Act. distance Indicates the currently measured distance between
the reference point of the sensor and the product
surface. Check the value:
•Value correct: Basic setup completed.
Return to the measured value display by pressing
several times
Value not incorrect: go back to step 7
("distance correction")
Status Used to enable, disable or delete a mapping
When using FDU90 with flooding protection tube: Parametrization of the flooding detection
Details, see "Description of Instrument Functions" BA00290F
10 Menu:
safety settings ->
safety distance
Safety dist. sensor 1
Safety dist. sensor 2
In order to detect flooding reliably when using the
FDU90 sensor with a flooding protection tube, a
safety distance must be defined slightly below the
lower edge of the flooding protection tube.
11 Menu:
relay/controls ->
relay allocation
Select the relay you want to use to indicate flooding
12 Relay N Function 1. Select "alarm diagnostics"
2. Select "diagnostics"
Allocation Select "safety distance channel 1/2".
The relay is de-energized as soon as the level rises
into the safety distance.