Prosonic S FMU90 Flow Measurement PROFIBUS Commissioning
Endress+Hauser 51
5.7.3 Linearization
Parameter Selection/Remarks
"type" Number and type of the parameters in this set depend on the selected linearization type.
Only the parameters "type" and "mode" are always present.
Select the linearization type in this parameter.
Selection
•None
In this linearization type the measured level is not converted but displayed in the selected
level unit (see "unit level").
Selection
•Linear
In this linearization type the displayed level is linear to the measured level.
The following additional parameters have to be specified.
Unit for the linearized value, e.g. kg, m3, ft3, ... ("customer unit")
Maximum capacity (a) of the vessel, measured in the customer unit ("maximum
scale").
100%
20
mA
0%
0/4
mA
(a)
kg
m
ft
3
3