Commissioning Prosonic S FMU90 Flow Measurement PROFIBUS
52 Endress+Hauser
"type" In these linearization types the measured level is convertet to the volume in a horizontal
cylinder or a spherical tank.
Selection
• Horizontal cylinder
1)
•Sphere
The following additional parameters have to be specified:
• Unit of the linearized value, e.g. kg, m3, ft3, ... ("customer unit")
• Diameter (D) of the tank ("diameter")
• Maximum capacity (a) of the tank, measured in the customer unit ("maximum scale")
In these linearization modes the measured level is converted to the volume in the
respective type of vessel.
Selection
• Angled bottom (A)
• Pyramid bottom (B)
• Conical bottom (B)
The following additional parameters have to be specified:
• Unit for the linearized value, e.g. kg, m3, ft3, ... ("customer unit")
• Intermediate height H according to the diagram ("intermediate height")
• Maximum capacity (a) of the tank, measured in the customer unit ("maximum
scale").
Parameter Selection/Remarks
100%
20
mA
0%
0/4
mA
(D)Ø
(a)
kg
m
ft
3
3
100%
20
mA
0%
0/4
mA
H
(a)
A
B
kg
m
ft
3
3