The "Relay/Controls" menu
80
8.1.5 "relay N (N = 1 - 6)"
(Part 3: Relay behavior)
"switch delay"
Use this parameter to specify the switch delay (in seconds).
The relay does not switch immediately after the switch on point has been exceeded but only after
the specified delay.
The measured value must exceed the switch-on point during the entire delay time.
"invert"
Use this parameter to specify if the switching direction of the relay is to be inverted.
Selection:
no (default)
The switching direction of the relay is not inverted. The relay switches as described in the above
sections.
yes
The switching direction of the relay is inverted. The states "energized" and "de-energized" are
interchanged as compared to the above description.
"error handling"
Use this parameter to specify the reaction of the relay in the case of an error.
Selection:
actual value
The relay switches according the the currently measured value (although its reliability is not
ensured).
hold (default)
The current switching state of the relay is maintained.
switch on
The relay is energized.
switch off
The relay is de-energized.
relay X RX104
switch delay:
invert:
error handling: