Set Current Output
Notes on Current Output:
The current output must be set in % or in the units of linearization.
Measuring Range Spread: The beginning and end of the current range can be set
as required with partial ranges of the total span also being assigned.
The current output can also be inverted so that the value in V0H5 is greater than that
in V0H6. An increased measured value will decrease the signal current.
Output Damping: The effect of the output damping is to attenuate the analog output
and the measuring indication on the display of the Prosonic T. When the liquid surface
is not steady, a steady reading can be obtained with the aid of the output damping.
0 s = without damping
1 to 255 s = with damping
Current on Fault (V0H7)
4 mA Threshold:
The 4 mA threshold ensures that no value falls below this during measurement.
Errors and Warnings in V9H0
E620: The current output is outside the set range (smaller than 3.8 mA, greater 20.5
mA). Check the calibration and settings of the current output.
Two Types of Measurement
Continuous Current Output
The current from 4 to 20 mA is assigned
to a measuring range.
Switch Current Output
The current values 4 and 20 mA or 8 and
16 mA are set as switchpoints.
4-wire 2-wire
4 to 20 mA, 4/20 mA, 8/16 mA
-10% 2.4 mA 3.8 mA
+110% 22 mA 22 mA
Height
4 mA 20 mA
V0H6 90%
V0H5 10%
# VH Entry Text
1 V8H1 e.g. 0 H Current output
0: linear 4 to 20 mA
1: linear 4 to 20 mA
with 4 mA threshold
2 V0H5 e.g. 10% H Level for 4 mA
3 V0H6 e.g. 90% H Level for 20 mA
4 V0H4 e.g. 20 s H Output damping
5 V0H7 e.g. 1 H Output on fault
0: -10%
1: +110%
2: HOLD (holds last
measured value)
# VH Entry Text
1 V8H1 e.g. 2 H Current output
2: digital 4/20 mA
3: digital 8/16 mA
2 V0H5 e.g. 10% H Switchpoint min.
4 or 8 mA
3 V0H6 e.g. 90% H Switchpoint max.
20 or 16 mA
4 V0H4 e.g. 10 s H Output damping
5 V0H7 e.g. 1 H Output on fault
0: -10%
1: +110%
2: HOLD (holds last measured
value)
Height
V0H6 90%
V0H5 10%
4 mA 20 mA
8 mA 16 mA