Prosonic T - FMU 130, 131, 230, 231, 232
Endress+Hauser
yes
yes
Expected
Actual
Expected
Actual
Measured value jumps Is the signal affected Increase output damping
sporadically with by turbulence or
see page 24.
constant level and agitator blades? With agitator blades in measuring
turbulence or agitator range, check sensor position.
blades.
see page 8-11, 25
.
Select application parameter
0 or 2 in V0H3.
See page 21
.
The measured value Multiple echoes? Select application parameter 2
jumps to a lower value in V0H3.
or remains continuously
See page 21.
too low with constant Select a larger first echo factor 1
level. or 2 in V3H4.
See page 26.