Parameter Setting up selections
Default
settings
Actual
Decimal point
DI DP
Number of decimal points
in the display
Selection range:
0 to 4 decimal points
9999,9
Display value 0%
DI LO
Display value at 0%
sensor value
Value:
-19999 to 99999
0,0
Display value 100%
DI HI
Display value at 100%
sensor value
Value:
-19999 to 99999
100,0
Offset
OFFST
Signal offset to match
measured value display
Value:
-19999 to 99999
0,0
Scale bargraph/
analogue output 0%
BG LO
Allocation of the numeric
display value to the
bargraph 0% value.
Selection range:
Display value 0% (
DI LO)to
Display value 100% (
DI HI)
0,0
When operating with the analogue output option this value is taken as the output
range start.
Scale bargraph/
analogue output 100% BG HI
Allocation of the numeric
display value to the
bargraph 100% value.
Selection range:
Display value 0% (
DI LO)to
Display value 100% (
DI HI)
100,0
When operating with the analogue output option this value is taken as the output
range end.
For the inverted signal output the 100% value is to be set smaller as the 0% value!
DISPL
5.2 Display