15.6 Device variables for multivariable devices
Multivariable measuring devices can transmit up to four device variables via HART
®
: the
Primary Variable (PV), Secondary Variable (SV), Tertiary Variable (TV) and Quaternary
Variable (QV).
Below you will find some examples of what default values can be set for these variables for
various sensors/actors:
Flowmeter, e.g. Promass:
Primary process variable (PV) -> Mass flow
Secondary process variable (SV) -> Totalizer 1
Third process variable (TV) -> Density
Fourth process variable (QV) -> Temperature
Temperature transmitter, e.g. TMT82:
Primary process variable (PV) -> Sensor 1
Secondary process variable (SV) -> Device temperature
Third process variable (TV) -> Sensor 1
Fourth process variable (QV) -> Sensor 1
For a level measuring device such as the Levelflex FMP5x, these four values can be as
follows:
Level measurement:
Primary process variable (PV) → Level linearized
Secondary process variable (SV) → Distance
Third process variable (TV) → Absolute echo amplitude
Fourth process variable (QV) → Relative echo amplitude
Interface measurement:
Primary process variable (PV) → Interface
Secondary process variable (SV) → Level linearized
Third process variable (TV) → Upper interface thickness
Fourth process variable (QV) → Relative interface amplitude
HART
®
actor, e.g. positioner:
Primary process variable (PV) -> Actuating value
Secondary process variable (SV) -> Valve set point
Third process variable (TV) -> Target position
Fourth process variable (QV) -> Valve position