RIA452 Commissioning
Endress+Hauser 23
6.3.3 Analog output - ANALOG OUT/M3
Bar rise Right
Left
Bar graph orientation.
• Right = 100% value (rising from left to right)
• Left = 100% value left (falling from left to right)
This item is only available if the "Analog output" option is available in your device.
Function
(menu
item)
Parameter setting Description
Ref. num. Input
Lintab
Selects which value is output at the analog output.
• Input = measured value
• Lintab = linearized measured value or current flow
rate for calculation of channel
Out damp 0..99.9
0.0
Signal damping of measuring input with 1st order low
pass. Time constant can be selected from 0 to 99.9 sec.
Out range Off
0 - 20 mA
4 - 20 mA
0 - 10 V
2 - 10 V
0 - 1 V
Signal type of output
"Off" switches the output signal off completely.
Dec. point XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
Number of places after the decimal point for
outputting the measured value. Can be selected for
analog signal types
Out 0% -99999..99999
0.0
Start value of the output signal
Out 100% -99999..99999
100.0
End value of the output signal
Offset -999.99..999.99
0.00
Shifts the zero point of the output curve in mA or V.
Fail mode Hold
const
Min
Max
Output value if a sensor or device error occurs.
• Hold = last valid value
• Const = freely selectable value
• Min = output value 3.5 mA for 4 to 20 mA,
otherwise 0 V or 0 mA
• Max = output value 22.0 mA for 0/4 to 20 mA,
otherwise 1.1 V or 11 V
Fail value 0..999.99
0.00
The freely selectable value for "Fail mode = Const" can
be set here.
Current output: 0 to 22 mA
Voltage output: 0 to 11 V
Function
(menu
item)
Parameter setting Description