The power of this function is that before the combination
(operative) each of the two inputs can be weighted with a factor
and the combination result can be set with a further offset.
What is important is that all values are entered in engineering
units.
Additionally the calculated value can be linearised over a max.
20 points using a third linearisation table. For this the setting
MCURV must be set to TABLE. The first and last points in the
table must be set to the following settings.
Enter of further points is done in
TAB M under NOM02, NOM03 etc.
(see linearisation table).
The linearisation value can also be moved using the setting
MDIOF.
Parameter Setting up selections
Default
settings
Actual
setting
* Operator
MAOP
Mathematics signal
combination of the analogue
inputs
OFF None
ADD Addition (+)
SUB Subtraction (-)
MUL Multiplication (x)
OFF
* Curve
MCURV
Select operating mode
LINAR Calculation without
linearisation table
TABLE Calculation using the
linearisation table
LINAR
* Decimal point factor 1 FADP1
Decimal point selection of the
multiplier for input 1
Selection range:
0 to 4 decimal points
9999,9
* Factor 1
FA1
Multiplier value for input 1 Value:
-19999 to 99999
1,0
* Decimal point factor 2 FADP2
Decimal point selection of the
multiplier for input 2
Selection range:
0 to 4 decimal points
9999,9
* Factor 2
FA2
Multiplier value for input 2 Value:
-19999 to 99999
1,0
MATH
Input value (X) with
decimal point from
MADP
Output value (Y) with
decimal point from
MDIDP
First point
MSCLO MDILO
Last point
MSCHI MDIHI
Process transmitter
52